The SINEAX AM3000 from Camille Bauer Metrawatt is a high-precision, multifunctional high-voltage power meter designed for panel mounting. The device was developed for the comprehensive measurement, analysis, and monitoring of electrical parameters in high-current power systems. With its high-resolution 5-inch TFT color display, intuitive menu navigation, and extensive analysis functions, it offers a reliable solution for monitoring and optimizing electrical power supply systems.
This universal measurement system supports various grid configurations, ranging from single-phase grids to unbalanced four-wire grids. It measures key electrical parameters such as voltage, current, active, reactive, and apparent power, power factor, frequency, as well as active and reactive energy. Additional functions for harmonic analysis, unbalance monitoring, and energy balance analysis enable a detailed assessment of the power system’s condition. This allows for the early detection of unusual loads, power system disturbances, and potential energy losses.
The SINEAX AM3000 is particularly well-suited for use in industrial production facilities, power distribution systems, switchgear, and building automation. Typical applications include continuous grid monitoring, energy management, the analysis of load profiles and energy consumption, and grid quality control. In addition, the device supports fault diagnosis, connection checks, and monitoring of electrical equipment.
Thanks to the integrated Ethernet and RS485 interfaces, the meter can be integrated into existing automation and control systems. The Modbus/TCP and Modbus/RTU communication protocols enable reliable transmission of the recorded measurement values. The integrated web server allows for convenient retrieval of measurement data and configuration of device settings without additional software.
The device model with part number 192833 is equipped with an integrated data logger that enables the periodic recording of electrical measurement values and the logging of events. This allows energy consumption, load profiles, and operating states to be documented and analyzed over extended periods. The stored data can be used for energy management, consumption optimization, and the retrospective analysis of grid events. Recorded data can be retrieved via the web interface and exported as CSV files as needed. In addition, load profile data can be automatically transferred to an SFTP server.
Comprehensive monitoring and alerting functions with individually configurable thresholds support the early detection of critical operating conditions. Security mechanisms such as role-based access control (RBAC), encrypted HTTPS communication, and audit logging also enable secure integration into modern energy and automation infrastructures.
Product Features:
- Manufacturer: Camille Bauer Metrawatt AG
- Product Series: SINEAX AM
- Model: SINEAX AM3000
- Part Number: 192833
- Device Type: Multifunctional Power Monitoring Meter
- Mounting type: Panel mounting
- Front dimensions: 144 × 144 mm
- Mounting Depth: 65.2 mm
- Display: 5.0-inch TFT color display
- Display resolution: 800 × 480 pixels
- Voltage and current inputs: 4 voltage channels and 4 current channels
- Rated current: 1 to 5 A, maximum 7.5 A
- Current overload capacity: 10 A continuous
- Rated voltage: 57.7 to 400 V (phase-to-neutral), 100 to 693 V (phase-to-phase)
- Rated frequency: 50/60 Hz, measurement ranges 42 to 58 Hz and 50.5 to 69.5 Hz
- Sampling rate: 18 kHz
- Measurement accuracy for voltage and current: ±0.1%
- Measurement accuracy for power: ±0.2%
- Measurement accuracy for frequency: ±0.01 Hz
- Active energy: Accuracy class 0.2S according to IEC 62053-22
- Reactive energy: Accuracy class 0.5S per IEC 62053-24
- Harmonic analysis: Up to the 50th harmonics according to IEC 61000-4-7
- Measurement functions: Voltage, current, power, frequency, energy, unbalance, and harmonic analysis
- Monitoring functions: 12 limit values, 8 monitoring functions, and 1 collective alarm
- Operating hour counters: 3 freely configurable operating hour counters and a device hour counter
- Communication interfaces: Ethernet (RJ45) and RS485
- Communication protocols: Modbus/TCP, Modbus/RTU, HTTP, HTTPS, NTP, IPv4, and IPv6
- Ethernet transmission: 10/100 Mbit/s
- Digital inputs and outputs: 1 digital input and 2 digital outputs
- Data logger: Integrated, for periodic data and event logging
- Storage medium: MicroSD card with at least 16 GB storage capacity
- Data logging: Load profiles, average power, energy meter readings, and events
- Recording intervals: Configurable from 10 seconds to 1 hour
- Data export: CSV files via web interface or REST API
- Automated data export: Transfer of load profile data to an SFTP server
- Power supply: 110 to 230 V AC / 130 to 230 V DC
- Power consumption: Maximum 30 VA or 13 W
- Operating temperature: -10 to +55 °C (without UPS)
- Relative humidity: Less than 95%, non-condensing
- Maximum operating altitude: 2,000 m above sea level
- Protection rating: IP54 on the front, IP30 for the housing, IP20 for the terminal blocks
- Protection class: II (insulated)
- Measurement category: Voltage 600 V CAT III, current 300 V CAT III
- Housing material: Polycarbonate (Makrolon)
- Weight: Approx. 800 g