The SINEAX AM1000 from Camille Bauer is a multifunctional high-current meter designed for panel mounting and developed for the precise measurement, analysis, and monitoring of electrical networks. With its compact 96 x 96 mm mounting format, a high-resolution 3.5-inch TFT color display, and intuitive menu navigation, it provides a clear overview of key electrical parameters.
The meter is suitable for universal use in industrial facilities, building automation, and electrical power distribution. Thanks to its flexible measurement inputs, it supports various network configurations, ranging from single-phase networks to unevenly loaded three- and four-wire networks. Among other things, it measures voltages, currents, active, reactive, and apparent power, power factors, frequencies, and energy values.
The SINEAX AM1000 offers numerous analysis functions for comprehensive power system monitoring. These include harmonic analysis up to the 50th harmonic, unbalance analysis, energy balancing, and graphical display of voltage and current waveforms. An integrated vector diagram simplifies phase sequence verification and enables the rapid detection of faulty connections.
The version with part number 192777 is designed for an auxiliary power supply of 100 to 230 V AC/DC and features Ethernet and RS485 interfaces, as well as a REST interface and Modbus communication. According to the order code, this is a device variant without an integrated data logger, intended for integration into a PME control center. This makes it particularly suitable for applications in which electrical measurement data is to be centrally recorded, processed, and evaluated, rather than permanently stored in the measuring device itself.
Connection to a PME control center enables the integration of the meter into a higher-level energy and power monitoring system. The recorded measurement values can be transmitted to central systems via the available communication interfaces and used there for analyzing energy consumption, monitoring electrical operating conditions, and evaluating power quality. The version without a data logger is therefore particularly suitable for systems in which centralized data storage is planned.
The integrated monitoring and alarm functions support the early detection of critical operating conditions. Individually configurable thresholds and logical links allow for targeted monitoring of electrical systems and protection of equipment. In addition, operating hour counters enable the monitoring of maintenance and service intervals.
Ethernet and RS485 communication interfaces are available for digital integration into higher-level automation and energy management systems. Supported protocols include Modbus/TCP, Modbus/RTU, and a REST interface. The integrated web interface allows users to retrieve current measurement data and configure device settings without additional software. Security features such as role-based access control (RBAC), HTTPS, and audit logging support secure operation in networked systems.
The SINEAX AM1000, with part number 192777, is thus a powerful solution for the continuous monitoring of electrical power distribution systems, the analysis of power quality, and the optimization of energy consumption. The combination of a 100–230 V AC/DC auxiliary power supply, versatile communication interfaces, and the intended integration into a PME control center makes the device particularly well-suited for centrally organized energy monitoring and energy management systems.
Product Features:
- Manufacturer: Camille Bauer Metrawatt AG
- Product Series: SINEAX AM
- Model: SINEAX AM1000
- Part Number: 192777
- Device Type: Multifunctional high-current and power monitoring meter
- Mounting type: Panel mounting
- Front dimensions: 96 x 96 mm
- Mounting depth: 85 mm
- Panel cutout: 92 x 92 mm
- Display: 3.5-inch TFT color display
- Display resolution: 320 x 240 pixels
- Voltage measurement channels: 3
- Current measurement channels: 3 current transformer inputs
- Rated current: 1 to 5 A
- Maximum measurement current: 7.5 A
- Current overload capacity: 10 A continuous; 100 A for 1 s, five times at 300-second intervals
- Rated voltage: 57.7 to 400 V (L-N), 100 to 693 V (L-L)
- Maximum input voltage: 480 V (L-N), 832 V (L-L)
- Rated frequency range: 42 to 58 Hz or 50.5 to 69.5 Hz
- Sampling rate: 18 kHz
- Measurement interval: 10/12 periods at 50/60 Hz; alternatively 1/2 period
- Measurement accuracy for voltage and current: ±0.2%
- Measurement accuracy for power: ±0.5%
- Frequency measurement accuracy: ±0.01 Hz
- Active energy accuracy: Class 0.5S according to IEC 62053-22
- Reactive energy accuracy: Class 0.5S according to IEC 62053-24
- Harmonic analysis: Up to the 50th harmonics according to IEC 61000-4-7
- Power system analysis: Voltage and current measurement, power analysis, unbalance analysis, reactive power analysis, energy balancing, THD and TDD analysis
- Monitoring functions: 12 limit values, 8 monitoring functions (each with 3 inputs), 1 collective alarm
- Operating hour counters: 1 device counter and 3 freely configurable operating hour counters
- Communication interfaces: Ethernet and RS485
- Ethernet connection: RJ45, 10/100 Mbit/s
- Communication protocols: Modbus/TCP, Modbus/RTU, REST, HTTP, HTTPS, NTP, IPv4, and IPv6
- REST interface: Available
- Web server: Integrated, for configuration and display of measured values
- Standard I/Os: 1 digital output and 1 digital input/output, passive
- Additional I/O expansions: None
- Data logger: Without integrated data logger
- PME control center: Device version for integration into a PME control center as specified by the order code
- Measurement data transmission: Via Ethernet and RS485 communication interfaces
- Auxiliary power: 100 to 230 V AC/DC
- Power supply type: Alternating or direct current (AC/DC)
- Power consumption: Maximum 18 VA or 8 W
- Operating temperature: -10 to +55 °C
- Storage temperature: -25 to +70 °C
- Relative humidity: Less than 95%, non-condensing
- Maximum operating altitude: 2,000 m above sea level
- Protection rating: IP54 (front), IP30 (housing), IP20 (terminals)
- Protection class: II (insulated)
- Measurement category: Voltage 600 V CAT III, Current 300 V CAT III
- Housing material: Polycarbonate (Makrolon)
- Flammability class: UL94 V-0
- Weight: Approx. 400 g
- Applications: Indoor use, industrial power distribution, building automation, energy management, grid monitoring, as well as centralized measurement data acquisition and energy monitoring with the PME control unit