#statusMessage#
Do you want to start the comparison now?
#statusMessage#
Do you want to start the comparison now?
How Thermography Enhances Manufacturing. Machine stoppages, component overheating, or electrical faults—unplanned downti...
Disturbances in the power grid often go unnoticed until systems shut down or equipment fails. Regular power quality asse...
In this practical checklist you will learn how to calibrate your measuring and test instruments effectively – simply, ef...
Modern oscilloscopes of the MXO Series from Rohde & Schwarz enable precise analysis and optimization of electric drivetr...
Manufacturer number: 050422
| Warranty (years): | 2 |
|---|---|
| Weight (kg): | 2.82 |
Battery-operated photovoltaic installation tester and characteristic curve measuring device for standard-compliant, mobile installation and repeat testing as well as for troubleshooting in grid-connected photovoltaic systems in accordance with VDE 0126-23 (DIN EN 62446) and for demonstrating performance data in accordance with VDE 0126-24 (DIN EN 61829). The Benning PV 2 is recommended for solar engineers, photovoltaic experts as well as service, cleaning and maintenance teams.
Before commissioning and after maintenance, check and document the functionality of the photovoltaic system in accordance with the provisions of VDE 0126-23 and check the PV system after cleaning or maintenance to guarantee optimal, low-loss functionality.
The test includes the continuity test of the protective and equipotential bonding conductors between the PV generator and the main ground terminal, measurement of the open circuit voltage and the short-circuit current in the PV string, and the insulation resistance between the active DC conductors (+/-) of the PV generator and earth. The Benning PV2 uses touch-protected measuring lines with standardized connectors for direct connection to PV modules or strings. The automatic test sequence warns of incorrect DC polarity and takes over all the necessary connections for safe measurement.
These tests can be carried out easily and quickly as well as reliably and safely with the Benning PV 2 photovoltaic installation tester.
The DIN VDE regulations govern the electrotechnical regulations as defined by DGUV V3 (accident prevention regulations f...
Thomas Schleich is an engineer, an expounder of ideas, a free spirit – and a first-class speaker at the dataTec Academy....