The Camille Bauer LINAX PQ5000-0311 0E0E is a stationary power quality analyser for continuous monitoring of electrical power systems. The series combines measurement of key electrical parameters with standards-based assessment of voltage events and network disturbances. Item 193065 is designed for DIN-rail installation.
The device measures voltages, currents, active, reactive and apparent power, frequency, power factor and active and reactive energy. Load profiles, unbalance and harmonics provide additional information about distribution networks and plant operation. This helps users monitor energy flows and investigate unusual electrical loads.
Power quality measurement complies with IEC 61000-4-30, class A. Class A methods allow standardised comparable power quality evaluations, including flicker and interharmonics. The device therefore supports regular network quality assessments and traceable documentation of operating conditions.
Events such as voltage dips, swells and interruptions can be assessed using recorded event data and time histories. Harmonic and unbalance analysis provides further evidence for identifying stressful operating conditions, supply disturbances and interactions between equipment and the electrical network.
The LINAX family supports conformity assessment against established requirements such as EN 50160. Measurements can be prepared through the device functions and transferred in PQDIF or CSV formats. Depending on the configuration, users can evaluate data through a web interface or integrate the analyser into an energy management or supervisory control system.
Communication is provided by Ethernet and RS485, including established protocols such as Modbus/TCP and Modbus/RTU. Further process and automation interfaces depend on the selected order code. The product family also includes security functions for access permissions, protected communications and traceable system operations.
This specific article 193065 is configured with auxiliary supply 100-230 V AC/DC; DIN-rail mounting without display, 4 Rogowski current inputs, PME wireless monitoring central unit. These characteristics determine the auxiliary supply, integration approach and available options. Add-on functions that are not documented for the ordered version should not be assumed to be included.
Typical applications include main low-voltage distribution boards, transformer substations, industrial power distribution and larger building installations. The LINAX PQ5000-0311 0E0E supplies both instantaneous electrical values and historical information on energy usage and power quality events.
Product features:
- Item number: 193065
- Device type: class A power quality analyser
- Product series: LINAX PQ5000
- Model / version: LINAX PQ5000-0311 0E0E
- Power quality class: Class A (IEC 61000-4-30)
- Network frequency: 50/60 Hz
- Sampling rate: 18 kHz
- Measurement channels: 4 I / 5 U
- Active energy accuracy class: 0.2S (IEC 62053-22)
- Measurement accuracy: U/I: +/-0.1 %
- Measured quantities: U, I, P, Q, S, f, active/reactive energy, unbalance, harmonics
- Functions: voltage dips, swells and interruptions; event recording
- Data export: PQDIF / CSV; web interface and export functions
- Communication interfaces: Ethernet and RS485
- Communication protocols: Modbus/TCP, Modbus/RTU, REST; other interfaces depend on the configuration
- Application: power distribution, power quality, load monitoring and energy management
- Auxiliary power supply: 100-230 V AC/DC
- Configuration feature: DIN-rail mounting without display
- Configuration feature: 4 Rogowski current inputs
- Configuration feature: PME wireless monitoring central unit
- Standard / measurement method: IEC 62586-1, IEC 61000-4-30
- Functions: voltage dips, interruptions and swells
- Functions: voltage and current harmonics
- Functions: unbalance analysis and frequency monitoring
- Functions: event lists and time-based evaluation
- Functions: analysis of load profiles and energy values
- Functions: comparison of readings with limit values
- Functions: conformity assessment against EN 50160
- Functions: power quality reporting support
- Functions: measurement data access via device web interface
- Data export: PQDIF for power quality evaluation
- Data export: CSV for measurement processing
- Communication interfaces: RJ45, 10/100 Mbit/s Ethernet
- Functions: integration into energy management systems
- Safety / protection: RBAC, HTTPS, audit logging (product family functions)
- Functions: monitoring of electrical distribution systems
- Functions: current and voltage harmonics, THD
- Functions: flicker and interharmonics (class A functions)
- Functions: power quality measurements to IEC 61000-4-30 class A
- Functions: voltage quality and supply events