The SINEAX AM1000 from Camille Bauer is a multifunctional high-current meter designed for panel mounting and developed for the precise measurement, analysis, and monitoring of electrical networks. With its compact 96 x 96 mm mounting format, a high-resolution 3.5-inch TFT color display, and intuitive menu navigation, it provides a clear overview of key electrical parameters.
The meter is suitable for universal use in industrial facilities, building automation, and electrical power distribution. Thanks to its flexible measurement inputs, it supports various network configurations, ranging from single-phase networks to unevenly loaded three- and four-wire networks. Among other things, it measures voltages, currents, active, reactive, and apparent power, power factors, frequencies, and energy values.
The SINEAX AM1000 offers numerous analysis functions for comprehensive power system monitoring. These include harmonic analysis up to the 50th harmonic, unbalance analysis, energy balancing, and graphical display of voltage and current waveforms. An integrated vector diagram simplifies phase sequence verification and enables the rapid detection of faulty connections.
The version with part number 192753 combines a 24–48 V DC auxiliary power supply with four additional analog outputs. These provide a bipolar output range of ±20 mA and enable the continuous transmission of selected electrical measured variables to higher-level control, regulation, and monitoring systems. The analog outputs support a linear or segmented linearized characteristic curve with up to nine inflection points and can be flexibly adapted to different process requirements.
The integrated monitoring and alarm functions support the early detection of critical operating conditions. Individually configurable limit values and logical links allow for targeted monitoring of electrical systems and protection of equipment. In addition, operating hour counters enable the monitoring of maintenance and service intervals.
Ethernet and RS485 communication interfaces are available for integration into higher-level automation and energy management systems. Modbus/TCP and Modbus/RTU, among others, are supported. Measurement data can be retrieved and device settings adjusted via the integrated web interface without the need for additional software. Security features such as role-based access control (RBAC), HTTPS, and audit logging ensure secure operation in networked systems.
The SINEAX AM1000, with part number 192753, is thus a powerful solution for the continuous monitoring of electrical power distribution systems, the analysis of power quality, and the optimization of energy consumption. Thanks to the combination of a 24- to 48-V DC auxiliary power supply and four analog outputs, the device is particularly well-suited for industrial automation systems and power distribution systems where electrical measurement values need to be continuously transmitted to external control and monitoring systems.
Product Features:
- Manufacturer: Camille Bauer Metrawatt AG
- Product Series: SINEAX AM
- Model: SINEAX AM1000
- Part Number: 192753
- Device Type: Multifunctional high-current and power monitoring meter with analog outputs
- Mounting type: Panel mounting
- Front dimensions: 96 x 96 mm
- Mounting depth: 85 mm
- Panel cutout: 92 x 92 mm
- Display: 3.5-inch TFT color display
- Display resolution: 320 x 240 pixels
- Voltage measurement channels: 3
- Current measurement channels: 3 current transformer inputs
- Rated current: 1 to 5 A
- Maximum measurement current: 7.5 A
- Current overload capacity: 10 A continuous; 100 A for 1 s, five times at 300-second intervals
- Rated voltage: 57.7 to 400 V (L-N), 100 to 693 V (L-L)
- Maximum input voltage: 480 V (L-N), 832 V (L-L)
- Rated frequency range: 42 to 58 Hz or 50.5 to 69.5 Hz
- Sampling rate: 18 kHz
- Measurement interval: 10/12 periods at 50/60 Hz; alternatively 1/2 period
- Measurement accuracy for voltage and current: ±0.2%
- Measurement accuracy for power: ±0.5%
- Frequency measurement accuracy: ±0.01 Hz
- Active energy accuracy: Class 0.5S according to IEC 62053-22
- Reactive energy accuracy: Class 0.5S according to IEC 62053-24
- Harmonic analysis: Up to the 50th harmonics according to IEC 61000-4-7
- Power system analysis: Voltage and current measurement, power analysis, unbalance analysis, reactive power analysis, energy balancing, THD and TDD analysis
- Monitoring functions: 12 limit values, 8 monitoring functions (each with 3 inputs), 1 collective alarm
- Operating hour counters: 1 device counter and 3 freely configurable operating hour counters
- Communication interfaces: Ethernet and RS485
- Ethernet connection: RJ45, 10/100 Mbit/s
- Communication protocols: Modbus/TCP, Modbus/RTU, HTTP, HTTPS, NTP, IPv4, and IPv6
- Web server: Integrated, for configuration and display of measured values
- Standard I/Os: 1 digital output and 1 digital input/output, passive
- Additional analog outputs: 4 channels, bipolar
- Analog output range: ±20 mA, maximum 24 mA
- Analog output accuracy: ±0.2% relative to 20 mA
- Maximum load on analog outputs: 500 Ω
- Linearization of analog outputs: Linear or with up to 9 inflection points
- Analog output functions: Measurement value transmission to control systems, process monitoring, and remote control
- Data logger: Includes periodic data recording and event logging
- Auxiliary power: 24 to 48 V DC
- Power supply type: Direct current (DC)
- Power consumption: Maximum 18 VA or 8 W
- Operating temperature: -10 to +55 °C
- Storage temperature: -25 to +70 °C
- Relative humidity: Less than 95%, non-condensing
- Maximum operating altitude: 2,000 m above sea level
- Protection rating: IP54 (front), IP30 (housing), IP20 (terminals)
- Protection class: II (insulated)
- Measurement category: Voltage 600 V CAT III, Current 300 V CAT III
- Housing material: Polycarbonate (Makrolon)
- Flammability class: UL94 V-0
- Weight: Approx. 400 g
- Applications: Indoor use, industrial power distribution, building automation, energy management, grid monitoring, and analog measurement data transmission to control and monitoring systems with a 24- to 48-V DC auxiliary power supply