Gossen Metrawatt METRALINE VC SENSE DC | AC/DC Current-Voltage Tester, 1,000 V AC / 1,500 V DC, 200 A AC / DC (M611U)

Manufacturer number: M611U

Gossen Metrawatt METRALINE VC SENSE DC | AC/DC Current-Voltage Tester, 1,000 V AC / 1,500 V DC, 200 A AC / DC, induct. Current Measurement, CAT IV 600V, CAT III 1000V (M611U).

Documents & Downloads

Description

METRALINE VC SENSE DC | AC/DC Current-Voltage Tester, 1,000 V AC / 1,500 V DC, 200 A AC / DC (M611U)

The Gossen Metrawatt METRALINE VC SENSE DC is a universally applicable test professional for the electrical trade, maintenance and industry. It combines two-pole voltage testing (AC/DC) with polarity display, contactless AC/DC current measurement, continuity/diode test, resistance and frequency measurement as well as rotary field determination - supplemented by bright measuring point illumination, acoustic/haptic feedback and automatic on/off function. Its slim design, IP64 protection and measurement category CAT IV 600 V/CAT III 1000 V ensure robust, safe use directly on systems and distribution boards.

Typical applications: fast voltage-free testing on sockets and terminals, polarity check in DC applications, non-contact current search on single-core conductors, cable search/cable break indication via sensor, rotary field test on three-phase plugs and rapid troubleshooting with illuminated 4-digit display. Test probes can be fixed to the fork at 19 mm intervals for socket outlet testing.

The M611U covers 1 VAC - 1000 VAC (TRMS, 15-400 Hz) and 1 VDC - 1500 VDC, measures currents from 0.1 A to 200 A (AC/DC) without contact and supports continuity, resistance, frequency and two-pole rotary field direction, among other things - ergonomically with illuminated 7-segment display, vibration and sound.

Technical product features:

  • Voltage test: 1 VAC ... 1,000 VAC (TRMS, 15-400 Hz) / 1 VDC ... 1,500 VDC, incl. polarity display.
  • Contactless current measurement: 0.1 A ... 200 A (AC/DC), frequency range 40-400 Hz; fork opening 14 mm.
  • Single-pole phase test: 100 ... 1,000 VAC (50/60 Hz); two-pole phase sequence test: 170 ... 1,000 V (40-70 Hz).
  • Continuity & diode test: acoustic continuity tone < 20 Ω; continuity range up to 500 kΩ (+50 %).
  • Resistance: 0 Ω ... 100 kΩ (resolution 1 Ω <2 kΩ / 1 kΩ >2 kΩ).
  • Frequency measurement: 0 ... 800 Hz.
  • Cable break detection: sensor search with indication in the display and acoustic signal.
  • Display & operation: 4-digit 7-segment display with illumination, LED scale (including 120/230/400/690/1000 V), data hold, zero, battery status, bright measuring point LED, vibration & sounder.
  • Measurement categories & standards: CAT IV 600 V, CAT III 1000 V, CAT II 1000 V; tested according to DIN EN 61243-3 and DIN EN 61010-1.
  • Degree of protection & environment: IP64; operation -15 ... +55 °C, storage -20 ... +70 °C, up to 85 % rH (non-condensing), altitude up to 2000 m.
  • Energy supply & automatic: 2× AAA (IEC LR03); auto-on at voltage/passage, auto-off after approx. 10 s.

About the Manufacturer

Gossen Metrawatt
Safety through competence. With over 100 years of experience, Gossen Metrawatt offers you unique products for measurement and testing technology as well as industrial metrology. The products stand for quality, reliability, safety and progressiveness, but also for dynamic and ergonomic design, high ease of use and unique innovative spirit.