The SINEAX AM3000 from Camille Bauer Metrawatt is a high-precision, multifunctional high-voltage power meter designed for panel mounting. The device was developed for the comprehensive measurement, analysis, and monitoring of electrical parameters in high-current power systems. With its high-resolution 5-inch TFT color display, intuitive menu navigation, and extensive analysis functions, it offers a reliable solution for monitoring and optimizing electrical power supply systems.
This universal measurement system supports various grid configurations, ranging from single-phase grids to unbalanced four-wire grids. It measures key electrical parameters such as voltage, current, active, reactive, and apparent power, power factor, frequency, as well as active and reactive energy. Additional functions for harmonic analysis, unbalance monitoring, and energy balance analysis enable a detailed assessment of the power system’s condition. This allows for the early detection of unusual loads, power system disturbances, and potential energy losses.
The SINEAX AM3000 is particularly well-suited for use in industrial production facilities, power distribution systems, switchgear, and building automation. Typical applications include continuous grid monitoring, energy management, the analysis of load profiles and energy consumption, and grid quality control. In addition, the device supports fault diagnosis, connection testing, and the monitoring of electrical equipment.
Thanks to its integrated Ethernet and RS485 interfaces, the meter can be integrated into existing automation and control systems. The Modbus/TCP and Modbus/RTU communication protocols enable reliable transmission of the recorded measurement values. The integrated web server allows for convenient access to measurement data and the ability to configure device settings without additional software.
The device model with part number 192865 also features two relay outputs with changeover contacts and an integrated PME wireless control center (Power Monitoring Energy). The relays enable the direct transmission of alarm messages and the control of external loads. The PME wireless control center allows additional current measurements to be recorded wirelessly and integrated into the energy monitoring system. Up to 33 PME wireless sensors with Rogowski coils can be connected for this purpose, enabling a total of up to 100 additional currents to be monitored. This functionality enables a detailed analysis of energy distribution and individual loads without the need for complex additional signal wiring.
The wireless PME technology is particularly well-suited for monitoring low-voltage feeders, sub-distribution panels, and individual loads in industrial facilities and buildings. The recorded current, power, and energy values enable a transparent representation of energy flows and form the basis for comprehensive energy management. Extensive alarm functions and security mechanisms such as role-based access control (RBAC), encrypted HTTPS communication, and audit logging support reliable and secure operation.
Product Features:
- Manufacturer: Camille Bauer Metrawatt AG
- Product Series: SINEAX AM
- Model: SINEAX AM3000
- Part Number: 192865
- Device Type: Multifunctional power monitoring meter with relay outputs and PME wireless control unit
- Mounting Type: Panel Mount
- Front Dimensions: 144 × 144 mm
- Mounting depth: 65.2 mm
- Display: 5.0-inch TFT color display
- Display resolution: 800 × 480 pixels
- Voltage and current inputs: 4 voltage channels and 4 current channels
- Rated current: 1 to 5 A, maximum 7.5 A
- Current overload capacity: 10 A continuous
- Rated voltage: 57.7 to 400 V (phase-to-neutral), 100 to 693 V (phase-to-phase)
- Rated frequency: 50/60 Hz, measurement ranges 42 to 58 Hz and 50.5 to 69.5 Hz
- Sampling rate: 18 kHz
- Measurement accuracy for voltage and current: ±0.1%
- Measurement accuracy for power: ±0.2%
- Measurement accuracy for frequency: ±0.01 Hz
- Active energy: Accuracy class 0.2S according to IEC 62053-22
- Reactive energy: Accuracy class 0.5S per IEC 62053-24
- Harmonic analysis: Up to the 50th harmonics according to IEC 61000-4-7
- Measurement functions: Voltage, current, power, frequency, energy, unbalance, and harmonic analysis
- Monitoring functions: 12 limit values, 8 monitoring functions, and 1 collective alarm
- Operating hour counters: 3 freely configurable operating hour counters and a device hour counter
- Communication interfaces: Ethernet (RJ45) and RS485
- Communication protocols: Modbus/TCP, Modbus/RTU, HTTP, HTTPS, NTP, IPv4, and IPv6
- Ethernet transmission: 10/100 Mbit/s
- Digital inputs and outputs: 1 digital input and 2 digital outputs
- Relay outputs: 2 relays with changeover contacts
- Relay rating: 250 V AC / 2 A or 30 V DC / 2 A
- Relay functions: Alarms, load control, and remote control
- PME wireless control center: Integrated, for wireless measurement of additional current and energy values
- PME wireless sensors: Connection of up to 33 sensors
- Additional current measurements: Up to 100 current readings via PME wireless sensors
- PME sensor technology: Rogowski coils with 3 or 4 measurement channels per sensor
- PME current measurement ranges: 250 A, 500 A, or 1,000 A, configurable
- PME radio frequency: 2.4 GHz
- PME radio range: Up to 10 m
- PME data encryption: AES-128
- PME measurement interval: 1 second
- PME sensor sampling rate: 6 kHz
- PME current measurement accuracy: ±0.5%
- PME energy measurement: Active and reactive energy, accuracy class 3
- PME measurement parameters: Current, THD, TDD, active, reactive, and apparent power, power factor, and cos φ
- PME data access: Modbus/RTU, Modbus/TCP, REST API, and CSV export
- PME Sensor Power Supply: Battery with a runtime of up to 10 years or USB-C
- PME Setup: Sensor registration via QR code
- Auxiliary power: 110 to 230 V AC / 130 to 230 V DC
- Power consumption: Maximum 30 VA or 13 W
- Operating temperature: -10 to +55 °C (without UPS)
- Relative humidity: Less than 95%, non-condensing
- Maximum operating altitude: 2,000 m above sea level
- Protection rating: IP54 on the front, IP30 for the housing, IP20 for the terminal blocks
- Protection class: II (insulated)
- Measurement category: Voltage 600 V CAT III, Current 300 V CAT III
- Housing material: Polycarbonate (Makrolon)
- Weight: Approx. 800 g